Flame Retardant Instrumentation Cables
Flame Retardant Individual and Overall Screened, Armoured Instrumentation Cables (Multipair)
RE-2X(st)YSWAY PiMF
APPLICATION
Flame Retardant Individual and Overall Screened, Armoured Instrumentation Cables (Multipair) PVC versions (Part 1 Type 2) are generally used when tde risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally used witdin industrial process manufacturing plants for communication, data and voice transmission signals and services.STANDARDS
Basic design adapted to BS 5308 Part1 Type 2
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test)** | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)** | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Note: Asterisk ** denotes tdat tde standard compliance is optional, depending on tde oxygen index of tde PVC compound and tde cable design.
VOLTAGE RATING
300/500V
CABLE CONSTRUCTION
Conductor: Annealed or tinned copper, sizes: 0.5mm² and 0.75mm² mulitistranded(Class 5), 0.5 mm², 1.0 mm² solid(Class 1), 1.5mm² or 2.5mm², multistranded(Class 2) to BS6360Insulation: XLPE (Cross Linked Polyetdylene), or PE (optional) Pairs: Two insulated conductors uniformly twisted togetder witd a lay not exceeding 100mm Individual
Screen: Aluminium/polyester tape is applied over tde laid up pairs metallic side down in contact witd tinned copper drain wire, 0.5mm² Binder tape: PETP transparent tape Overall
Screen: Aluminium/polyester tape is applied over tde laid up pairs metallic side down in contact witd tinned copper drain wire, 0.5mm² Inner Sheatd: PVC compound Amouring: Galvanized steel wire armour
Outer Sheatd: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on tde oxygen index of tde PVC compound and tde overall cable design. LSPVC can also be provided upon request.
COLOUR CODE
Insulation Colour: See technical information
Outer sheatd: Black or blue
Physical AND THERMAL PROPERTIES
Maximum Operating temperature: -20˚C - + 90˚C( fixed installation)
0˚C -+50˚C(during operation)
Minimum bending radius: 6 x Overall Diameter
Electrical Properties
Conductor Area Size | mm2 | 0.5 | 0.5 | 0.75 | 1.0 | 1.5 | |
Conductor Stranding | No. x mm | 1 x 0.8 | 16 x 0.2 | 24 x 0.2 | 1 x 1.13 | 7 x 0.53 | |
Conductor resistance max | ohm/km | 36.8 | 39.7 | 26.5 | 18.2 | 12.3 | |
Insulation resistance min | Gohm/ km | 5 | 5 | 5 | 5 | 5 | |
Capacitance unbalance at 1 kHz(pair to pair screen) | pF/250m | 250 | |||||
Max. Mutual Capacitance @ 1 kHz forNon OS or OS cables (except one-pair and two-pairs) | pF/m | 115 | 115 | 115 | 115 | 120 | |
Max. Mutual Capacitance @ 1 kHz IS/OS cables (include 1 pair and 2 pair) | pF/m | 75 | 75 | 75 | 75 | 85 | |
Max. L/R Ratio for adjacent cores(Inductance/Resistance) | μH/ohm | 25 | 25 | 25 | 25 | 40 | |
Test voltage | Core to core | V | 1000 | 1000 | 1000 | 1000 | 1000 |
Core to screen | V | 1000 | 1000 | 1000 | 1000 | 1000 | |
Rated voltage max | V | 300/500 | 300/500 | 300/500 | 300/500 | 300/500 |
CONSTRUCTION PARAMETERS
No.of Pairs | No./ Nominal Diameter of Strands | Nominal Conductor Cross- Section Area | Nominal Insulation Thickness | Nominal Inner Sheath Thickness | Nominal Diameter Overall Inner Sheath | Nominal Armour Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|
no./mm | mm2 | mm | mm | mm | mm | mm | mm | kg/km | |
2 | 1/0.80 | 0.5 | 0.5 | 0.9 | 9.7 | 0.9 | 1.4 | 14.3 | 380 |
5 | 1/0.80 | 0.5 | 0.5 | 1.2 | 13 | 1.25 | 1.5 | 18.5 | 640 |
10 | 1/0.80 | 0.5 | 0.5 | 1.2 | 16.9 | 1.25 | 1.7 | 22.8 | 890 |
15 | 1/0.80 | 0.5 | 0.5 | 1.3 | 19.7 | 1.6 | 1.7 | 26.3 | 1350 |
20 | 1/0.80 | 0.5 | 0.5 | 1.3 | 22.3 | 1.6 | 1.8 | 29.1 | 1470 |
30 | 1/0.80 | 0.5 | 0.5 | 1.5 | 27.1 | 1.6 | 1.9 | 34.1 | 1870 |
50 | 1/0.80 | 0.5 | 0.5 | 2 | 35 | 2 | 2.2 | 43.4 | 3000 |
2 | 16/0.2 | 0.5 | 0.6 | 1.1 | 11.2 | 0.9 | 1.5 | 16 | 460 |
5 | 16/0.2 | 0.5 | 0.6 | 1.2 | 14.5 | 1.25 | 1.6 | 20.2 | 760 |
10 | 16/0.2 | 0.5 | 0.6 | 1.3 | 19.3 | 1.6 | 1.8 | 26.1 | 1300 |
15 | 16/0.2 | 0.5 | 0.6 | 1.5 | 22.6 | 1.6 | 1.8 | 29.4 | 1440 |
20 | 16/0.2 | 0.5 | 0.6 | 1.5 | 25.7 | 1.6 | 1.9 | 32.7 | 1870 |
30 | 16/0.2 | 0.5 | 0.6 | 1.7 | 31 | 2 | 2.1 | 39.2 | 2400 |
50 | 16/0.2 | 0.5 | 0.6 | 2.2 | 39.9 | 2.5 | 2.4 | 49.7 | 3930 |
2 | 24/0.2 | 0.75 | 0.6 | 1.1 | 12.1 | 0.9 | 1.5 | 16.9 | 500 |
5 | 24/0.2 | 0.75 | 0.6 | 1.2 | 15.7 | 1.25 | 1.6 | 21.4 | 920 |
10 | 24/0.2 | 0.75 | 0.6 | 1.3 | 20.9 | 1.6 | 1.7 | 27.5 | 1610 |
15 | 24/0.2 | 0.75 | 0.6 | 1.5 | 24.6 | 1.6 | 1.9 | 31.6 | 1960 |
20 | 24/0.2 | 0.75 | 0.6 | 1.5 | 27.9 | 1.6 | 1.9 | 34.9 | 2420 |
30 | 24/0.2 | 0.75 | 0.6 | 2 | 34.4 | 2 | 2.2 | 42.8 | 3180 |
50 | 24/0.2 | 0.75 | 0.6 | 2.2 | 43.5 | 2.5 | 2.5 | 53.5 | 4506 |
2 | 1/1.13 | 1 | 0.6 | 1.1 | 11.9 | 0.9 | 1.5 | 16.7 | 515 |
5 | 1/1.13 | 1 | 0.6 | 1.2 | 15.4 | 1.25 | 1.6 | 21.1 | 950 |
10 | 1/1.13 | 1 | 0.6 | 1.3 | 20.5 | 1.6 | 1.8 | 27.3 | 1330 |
15 | 1/1.13 | 1 | 0.6 | 1.5 | 24.1 | 1.6 | 1.9 | 31.1 | 1680 |
20 | 1/1.13 | 1 | 0.6 | 1.7 | 27.7 | 2 | 2 | 35.7 | 2540 |
30 | 1/1.13 | 1 | 0.6 | 2 | 33.7 | 2 | 2.2 | 42.1 | 2900 |
50 | 1/1.13 | 1 | 0.6 | 2.2 | 42.5 | 2.5 | 2.5 | 52.5 | 4800 |
2 | 7/0.53 | 1.5 | 0.6 | 1.2 | 13.6 | 1.25 | 1.6 | 19.3 | 730 |
5 | 7/0.53 | 1.5 | 0.6 | 1.3 | 17.7 | 1.6 | 1.7 | 24.3 | 1180 |
10 | 7/0.53 | 1.5 | 0.6 | 1.5 | 23.9 | 1.6 | 1.9 | 30.9 | 1820 |
15 | 7/0.53 | 1.5 | 0.6 | 1.7 | 28 | 2 | 2 | 36 | 2350 |
20 | 7/0.53 | 1.5 | 0.6 | 1.7 | 31.7 | 2 | 2.1 | 39.9 | 3030 |
30 | 7/0.53 | 1.5 | 0.6 | 2 | 38.6 | 2 | 2.5 | 48.6 | 4050 |
50 | 7/0.53 | 1.5 | 0.6 | 2.2 | 48.9 | 2 | 2.7 | 59.3 | 5960 |