Caledonian Airport Cables

Airport Primry Circuit Lighting Cables

Airport 400Hz Cables

Airport Series Runway Lighting Cables

Airport Lighting Fire Resistant Cables

Airport Lighting Flame Retardant Cables

Baggage Handling System Cables

FAS (Fire Alarm System)

  • Detector Cable
  • Fire Communication Cable
  • Sounder Cable
  • Control Cable
  • RS485 Data Cable

SACS (Security Access Control System)

  • RS485 Data Cables
  • Push Button Cables
  • Lock Cables
  • Card Reader Cables

CCTV (Closed Circuit TV)

  • Video Cables
  • RS485 Data Cables

PAS (Public Address System)

  • Loudspeaker Cables
  • RS485 Data Cables

BMS (Building Management System)

  • Digital Signal Cables
  • Analog Signal Cables
  • RS485 Data Cables
  • Temperature Control Cables

CPMS (Car Park Management System)

  • Communication Cables
  • Talk-back Cables

BS 7629-1 600/1000V SR Insulated Flexibles Control Cables (2-4 Cores & Multicore)

FFX400 1SZ1-R(PH60)(CU/SR/LSZH 600/1000V Class 2)

FFX400 1SZ1-F(PH60)(CU/SR/LSZH 600/1000V Class 5)

BS 7629 standard SR insulated flexibles control cable

Applications

BS 7629 standard SR insulated flexibles control cables are designed for power supply and signals trasmission, indoor or outdoor even wet environment. They are designed for fixed laying in free air, in pipe or conduit, on masonry and metal structures or suspended in places where in case of fire people are exposed to serious risks for emission of smoke, toxic and corrosive gases and where you want to avoid damage to facilities, equipment, goods. They are primarily intended for feeding of: emergency exits, alarm signals, warning of smoke or gas, escalators.

Standards

BS 7629-1

FIRE PERFORMANCE

Circuit Integrity IEC 60331-23; BS 6387 CWZ; DIN VDE 0472-814(FE180); CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)
System circuit integrity DIN 4102-12, E30 depending on lay system
Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454

Construction

Conductor Plain annealed copper wire, stranded according to IEC 60228 class 2
Insulation Mica glass fire resistant tape covered by fire resistant silicone rubber compound type EI2 as per BS 7655-1.1.
Cabling The cores are cabled together in concentric layers with suitable non-hygroscopic fillers.
Sheath Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

Colour Code

Insulation Colour as per BS7671

  With Earth Conductor
Without Earth Conductor
2Cores Brown, Blue  
3Cores Yellow/Green, Brown, Blue Brown, Gray, Black
4Cores Yellow/Green, Brown, Gray, Black Brown, Gray, Black, Blue
5Cores Yellow/Green, Brown, Gray, Black, Blue Brown, Gray, Black, Blue, Black
above 5 Cores Yellow/Green, Black Numbered Black Numbered
Sheath Colour: Black (other colors upon request)

Physical and thermal properties

Temperature range during operation (fixed state) -30°C – +90°C
Temperature range during installation (mobile state) -20°C – +50°C
Minimum bending radius 8 x Overall Diameter

Electrical properties

Rated Voltage Uo/U (Um) 600/1000V
Dielectric test 3500 V r.m.s. x 5' (core/core)
Insulation resistance 300 MΩ x km (at 20°C)
Short circuit temperature 350°C

Dimensions and Weight

Cable Code No. of Core X Cross Section Nominal Insulation Thickness Nominal Sheath Thickness Nominal Overall Diameter Approx. Weight
  mm2 mm mm mm kg/km
2 core
FFX400 1SZ1-R(PH60) 2x1.5 1.0 1.2 9,2 124
FFX400 1SZ1-R(PH60) 2x2.5 1.1 1.3 10,0 155
FFX400 1SZ1-R(PH60) 2x4.0 1.1 1.4 11,2 207
FFX400 1SZ1-R(PH60) 2x6.0 1.1 1.5 13,1 298
FFX400 1SZ1-F(PH60) 2x10 1.1 1.6 15,9 441
FFX400 1SZ1-F(PH60) 2x16 1.1 1.7 17,4 602

3 core

FFX400 1SZ1-F(PH60) 3x1.5 1.0 1.2 9,8 148
FFX400 1SZ1-F(PH60) 3x2.5 1.1 1.3 10,6 188
FFX400 1SZ1-F(PH60) 3x4.0 1.1 1.4 12,1 263
FFX400 1SZ1-F(PH60) 3x6.0 1.1 1.5 14,4 372
FFX400 1SZ1-F(PH60) 3x10 1.1 1.6 16,8 541
FFX400 1SZ1-F(PH60) 3x16 1.1 1.7 19,4 777

4 core

FFX400 1SZ1-F(PH60) 4x1.5 1.0 1.3 10,6 176
FFX400 1SZ1-F(PH60) 4x2.5 1.1 1.4 11,5 228
FFX400 1SZ1-F(PH60) 4x4.0 1.1 1.5 13,6 332
FFX400 1SZ1-F(PH60) 4x6.0 1.1 1.6 11,5 214
FFX400 1SZ1-F(PH60) 4x10 1.1 1.7 18,5 680
FFX400 1SZ1-F(PH60) 4x16 1.1 1.8 21,2 973

5 core

FFX400 1SZ1-F(PH60) 5x2.5 1.1 1.4 12,6 266
FFX400 1SZ1-F(PH60) 5x4.0 1.1 1.5 14,5 399
FFX400 1SZ1-F(PH60) 5x6.0 1.1 1.6 17,6 576
FFX400 1SZ1-F(PH60) 5x10 1.1 1.7 20,5 850
FFX400 1SZ1-F(PH60) 5x16 1.1 1.8 23,3 1202

 

If you have any questions please contact us.

E-mail: enquiry@airport-cables.com
Site: http://www.airport-cables.com

27 Old Gloucester Street, London, WC1N 3AX UK

Tel: 44-207-4195087

Fax: 44-207-8319489

Enquiry: sales@airport-cables.com