IEC 60502-1/BS 6724 Single Core 600/1000V Mica+XLPE Insulated, Armoured LSZH Sheathed Power Cables
Applications
IEC 60502-1/BS 6724 armoured single core 600/1000V fire resistant power cables is used in fire extinguishing systems, sprinklers, control panels, and exit lights in high-rise buildings, hotels, hospitals, sub-ways, and public facilities.
Standards
IEC 60502-1 / BS 6724
Fire Performance
Circuit Integrity | IEC 60331-23; BS 6387 CWZ; DIN VDE 0472-814(FE180); CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) |
System circuit integrity | DIN 4102-12, E30 depending on lay system |
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Construction
Conductor | Plain annealed copper wire, stranded according to IEC 60228 class 2 |
Fire Barrier | Mica glass tape covered by extruded cross-linked XLPE compound |
Insulation | Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. |
Colour Code
Insulation Colour as per BS7671
With Earth Conductor | Without Earth Conductor |
|
2Cores | Brown, Blue | |
3Cores | Yellow/Green, Brown, Blue | Brown, Gray, Black |
4Cores | Yellow/Green, Brown, Gray, Black | Brown, Gray, Black, Blue |
5Cores | Yellow/Green, Brown, Gray, Black, Blue | Brown, Gray, Black, Blue, Black |
above 5 Cores | Yellow/Green, Black Numbered | Black Numbered |
Sheath Colour: Black (other colors upon request)
Physical and thermal properties
Temperature range during operation (fixed state) | -30°C – +90°C |
Temperature range during installation (mobile state) | -20°C – +50°C |
Minimum bending radius | 10 x Overall Diameter |
Electrical properties
Rated Voltage Uo/U (Um) | 600/1000V |
Dielectric test | 3500 V r.m.s. x 5' (core/core) |
Insulation resistance | 20 MΩ x km (at 20°C) |
Short circuit temperature | 250°C |
Dimensions and Weight
Conductor | FFX300 1mRMZ1-R | ||||
---|---|---|---|---|---|
Nominal Cross Section Area | No./ Nominal Diameter of Strands | Dia. of Conductor | Nominal Insulation Thickness | ||
Approx. Overall Diameter | Approx. Weight | ||||
mm2 | No./mm | mm | mm | mm | kg/km |
1.5 | 7/0.53 | 1.59 | 0.7 | - | - |
2.5 | 7/0.67 | 2.01 | 0.7 | - | - |
4 | 7/0.85 | 2.55 | 0.7 | - | - |
6 | 7/1.04 | 3.12 | 0.7 | - | - |
10 | 7/1.35 | 4.05 | 0.7 | - | - |
16 | 7/1.70 | 5.1 | 0.7 | - | - |
25 | 7/2.14 | 6.42 | 0.9 | - | - |
35 | 19/1.53 | 7.65 | 0.9 | - | - |
50 | 19/1.78 | 8.9 | 1 | 18.5 | 780 |
70 | 19/2.14 | 10.7 | 1.1 | 20.5 | 1010 |
95 | 19/2.52 | 12.6 | 1.1 | 23 | 1320 |
120 | 37/2.03 | 14.21 | 1.2 | 24.5 | 1610 |
150 | 37/2.25 | 15.75 | 1.4 | 27 | 2010 |
185 | 37.2.52 | 17.64 | 1.6 | 29.5 | 2440 |
240 | 61/2.25 | 20.25 | 1.7 | 34.5 | 3060 |
300 | 61/2.52 | 22.68 | 1.8 | 36.9 | 3690 |
400 | 65/2.85 | 25.65 | 2 | 41.5 | 4780 |
500 | 61/3.20 | 28.8 | 2.2 | 45.5 | 5970 |
630 | 127/2.52 | 32.76 | 2.4 | 50.5 | 7530 |
800 | 127/2.85 | 37.05 | 2.6 | 56.8 | 9680 |
1000 | 127/3.20 | 41.6 | 2.8 | 61.5 | 11980 |